分类
特 点 Features
● 工业逆变器和电机驱动的EMC解决方案。
EMC solutions for industrial inverters and motor drives.
● 漏电流小,底板式安装,简单方便。Small leakage current,
floor type installation, simple and convenient.
● 良好的共模和差模干扰衰减性能。Good common mode and
differential mode interference attenuation performance.
● 结构紧凑,体积小,性价比高。Compact structure, small size,
high cost performance.
应 用 Application
● 三相电机驱动。Three phase motor drive.
● 工业自动化。Industrial automation.
● 不间断电源。UPS
●开关模式电源。SMPS
性能指标 Characteristcs
额定电压Rated voltage | 440/250VAC |
工作频率 Operating Frequency | DC~60Hz |
额定电流Rated curren | 5~200A@40℃max. |
耐压试验 (60s) Test Voltage | 1500VDC(线-线Line - line) 2250VDC(线-地Line - ground) 3000VDC/2S |
气候类别 Climate category | 40/100/21 |
产品型号表 Filter Table
型号 model | 接线方式:输入输出 | 额定电流A Rated curren | 接地电容量nF Grounding capacity | MAX泄漏电流 * leakage current 440VAC/50Hz | 电路图Fig. Circuit diagram | 外形尺寸Fig. Outline Drawing | ||
YX-322-5- | TT | 5 | 22 | <1mA | 1 | 1 | ||
YX-322-10- | TT | 10 | 22 | <1mA | 1 | 1 | ||
YX-322-16- | TT | 16 | 22 | <1mA | 1 | 1 | ||
YX-322-20- | TT | 20 | 50 | <2mA | 1 | 2 | ||
YX-322-25- | SS | 25 | 50 | <2mA | 1 | 2 | ||
YX-322-35- | SS | 35 | 50 | <2mA | 1 | 3 | ||
YX-322-50- | SS | 50 | 50 | <2mA | 1 | 3 | ||
YX-322-65- | SS | 65 | 50 | <2mA | 1 | 3 | ||
YX-322-80- | SS | 80 | 50 | <4mA | 2 | 4 | ||
YX-322-100- | SS | 100 | 50 | <4mA | 2 | 4 | ||
YX-322-130- | SS | 130 | 50 | <4mA | 2 | 4 | ||
YX-322-160- | SS | 160 | 50 | <4mA | 2 | 4 | ||
YX-322-200- | SS | 200 | 50 | <4mA | 2 | 5 | ||
*注意:如果在缺两相这种蕞坏的状况下,其漏电流将比正常状态高7.7倍左右 Note: in the worst case of lack of two phases, the leakage current will be about 7.7 times higher than the normal state |
电原理图Typical Circuit Diagram
Fig.1 Fig.2
插入损耗 Insertion LOSS in dB (50Ω测量系统,IEC/CISPR No.17号出版物)
5A 10A 16A
20A 25A 35A
50A 65A 80A
100A 130A 160A~200A
外形尺寸图 Outline Drawing : mm
Fig.1 (5A~16A) Fig.2 (20A~25A)
Fig.3 (35A~65A) Fig.4 (80A~160A)
Fig.5 (200A)